34-38-34. Delivery and dispensing operations to comply with International Fire Code--Determining liquid level--Equipment requirements.
Delivery operations shall comply with applicable requirements of chapter 57 of the International Fire Code, 2015 edition. Dispensing operations shall comply with the provisions of chapter 57 of the International Fire Code, 2015 edition.
The delivery vehicle shall be separated from any aboveground tank by at least twenty-five feet.
Means shall be provided for determining the liquid level in each tank and this means shall be accessible to the delivery operator. Provisions shall be made either to automatically stop the delivery of fuel to the tank if the liquid level in the tank reaches ninety-five percent capacity or to sound an audible alarm if the liquid level in the tank reaches ninety percent capacity.
A check valve, gate valve with quick-connect coupling, or a dry-break valve shall be installed in the piping at the point where connection and disconnection is made for delivery from a vehicle to any aboveground tank. This device shall be protected against tampering and physical damage.
If the delivery hose is connected directly to the tank, the fill line at the tank shall be equipped with a tight-fill device for connecting the hose to the tank.
Source: SL 1991, ch 269, §12; SL 2006, ch 185, §8; SL 2010, ch 177, §6; SL 2016, ch 181, §6.
Structure South Dakota Codified Laws
Title 34 - Public Health and Safety
Chapter 38 - Flammable And Combustible Liquids
Section 34-38-2.1 - Self-service pumps--Latch-open device permitted.
Section 34-38-23 - Definition of terms.
Section 34-38-24 - Installation of aboveground storage tanks--Approval.
Section 34-38-26 - Compliance with International Fire Code.
Section 34-38-28 - Location requirements for aboveground tanks.
Section 34-38-29 - Spill control to be in accordance with International Fire Code.
Section 34-38-31 - Protection against vehicular collision.
Section 34-38-32 - Maintenance of area within any dike.
Section 34-38-33 - Tank piping system in contact with soil--Protection from corrosion.
Section 34-38-35 - Promulgation of rules.
Section 34-38-36 - Power of local governments as to zoning unaffected.
Section 34-38-37 - Review of actions by director--Director's decision appealable.
Section 34-38-38 - Application to facilities constructed after July 1, 2016.