Section 34-38-30 - Impermissible methods for dispensing fuel from aboveground tank--Equipment requirements as to tanks--Failure to comply as misdemeanor.

34-38-30. Impermissible methods for dispensing fuel from aboveground tank--Equipment requirements as to tanks--Failure to comply as misdemeanor.
No person may dispense fuel from an aboveground storage tank by either gravity flow or pressurization of the tank. The owner of an aboveground storage tank shall prevent the release of liquid from the tank by syphon flow.
If an aboveground storage tank is at an elevation that produces a gravity head on the dispensing device, the tank outlet shall be equipped with a device such as a normally-closed solenoid valve that will prevent gravity flow from the tank to the dispenser. This device shall be located adjacent to and downstream of the outlet valve. The device shall be installed and adjusted so that liquid cannot flow by gravity from the tank to the dispenser if the piping or hose fails.
If a submersible pump system is used, a listed rigidly anchored emergency shutoff valve, incorporating a fusible link or other thermally actuated device which is designed to close automatically in the event of severe impact or fire exposure, shall be installed in accordance with the manufacturer's instructions in the supply line at the base of each individual island-type dispenser or at the inlet of each overhead dispensing device. An emergency shutoff valve incorporating a slip joint feature may not be used. The automatic closing feature of this valve shall be checked at the time of initial installation and at least once a year thereafter by manually tripping the hold-open linkage.
If a suction pump-type dispensing device is used, a listed, vacuum-actuated shut-off valve, with a shear section, or an equivalent-type valve shall be installed directly beneath each dispensing device.
Shut-off and check valve shall be equipped with a pressure-relieving device to relieve the pressure generated by thermal expansion back to the tank and piping shall be routed so that exposure to physical damage is minimized.
A violation of this section is a Class 2 misdemeanor.

Source: SL 1991, ch 269, ยง8.

Structure South Dakota Codified Laws

South Dakota Codified Laws

Title 34 - Public Health and Safety

Chapter 38 - Flammable And Combustible Liquids

Section 34-38-2.1 - Self-service pumps--Latch-open device permitted.

Section 34-38-23 - Definition of terms.

Section 34-38-24 - Installation of aboveground storage tanks--Approval.

Section 34-38-25 - Letter of approval required before proposed construction begins--Letter and plans to be submitted to division.

Section 34-38-26 - Compliance with International Fire Code.

Section 34-38-27 - Aboveground storage tank to be listed for such use--Underground tanks not to be installed aboveground--Failure to comply as misdemeanor.

Section 34-38-28 - Location requirements for aboveground tanks.

Section 34-38-29 - Spill control to be in accordance with International Fire Code.

Section 34-38-30 - Impermissible methods for dispensing fuel from aboveground tank--Equipment requirements as to tanks--Failure to comply as misdemeanor.

Section 34-38-31 - Protection against vehicular collision.

Section 34-38-32 - Maintenance of area within any dike.

Section 34-38-33 - Tank piping system in contact with soil--Protection from corrosion.

Section 34-38-34 - Delivery and dispensing operations to comply with International Fire Code--Determining liquid level--Equipment requirements.

Section 34-38-35 - Promulgation of rules.

Section 34-38-36 - Power of local governments as to zoning unaffected.

Section 34-38-37 - Review of actions by director--Director's decision appealable.

Section 34-38-38 - Application to facilities constructed after July 1, 2016.

Section 34-38-39 - Limitations as to tank capacity.