RCW 19.27.720
Inspections and tests—Qualifications—Report—Penalty.
(1) Inspections and tests under this section must be performed by a contractor or engineer with the following qualifications:
(a) For inspection and testing of fire dampers, smoke dampers, and combination fire and smoke dampers, such inspector must have a current and valid certification to inspect and test fire dampers, smoke dampers, and combination fire and smoke dampers and hold certification from the international certification board as a fire life safety 1 or fire and smoke damper technician through a program accredited by the American national standards institute under the ISO/IEC 17024 standard.
(b) For inspection and testing of smoke control systems, such inspector must have a current and valid certification from the international certification board as a fire life safety 2 or smoke control system technician through a program accredited by the American national standards institute under the ISO/IEC 17024 standard.
(2) A building engineer or other person knowledgeable with the building system must be available in person or by phone to the inspector during the inspection and testing in order to provide building and systems access and information.
(3) If an inspection reveals compliance with the requirements of this section, the inspector shall issue a certificate of compliance, which includes the name of the inspector and the inspector's employer; the name of the building owner and address of the property; the location of all smoke dampers, fire dampers, combination fire and smoke dampers, and smoke control systems inspected or tested; and the date of the inspection or test.
(4) In the event an inspection or test reveals deficiencies in smoke dampers, fire dampers, combination fire and smoke dampers, or smoke control systems, the inspector shall prepare a deficiency report for the building owner identifying the nature of the deficiency and the reasons for noncompliance. The building owner shall, within one hundred twenty days of the date of the inspection, take necessary steps to ensure the defective equipment is replaced or repaired and reinspected to ensure that the deficiency is corrected and is in compliance with the requirements of all applicable standards pursuant to chapter 88, Laws of 2020. The authority having jurisdiction shall have the authorization to extend the compliance period. The building owner shall provide documentation of when and how the deficiencies were corrected. If the building owner does not correct the deficiency within one hundred twenty days of the date of the inspection, the local authority may issue a citation as described in RCW 19.27.740.
(5) In addition to identifying the location and nature of a deficiency, the report shall contain the name of the inspector and the inspector's employer; the name of the building owner; address of the property; the location of all fire dampers, smoke dampers, combination fire and smoke dampers, and smoke control systems inspected or tested; and the date of the inspection or test.
(6) Tests and inspections of fire dampers, smoke dampers, combination fire and smoke dampers, and smoke control systems shall be conducted in accordance with the technical specifications and required time periods specified by national fire protection association standards 80, 90a, 90b, 92, and 105, as applicable.
[ 2020 c 88 § 3.]
NOTES:
Effective date—2020 c 88: See note following RCW 19.27.700.
Structure Revised Code of Washington
Title 19 - Business Regulations—Miscellaneous
Chapter 19.27 - State Building Code.
19.27.020 - Purposes—Objectives—Standards.
19.27.031 - State building code—Adoption—Conflicts—Opinions.
19.27.035 - Process for review.
19.27.040 - Cities and counties authorized to amend state building code—Limitations.
19.27.042 - Cities and counties—Emergency exemptions for housing for indigent persons.
19.27.060 - Local building regulations superseded—Exceptions.
19.27.067 - Temporary worker housing—Exemption—Standards.
19.27.070 - State building code council—Established—Membership—Travel expenses.
19.27.074 - State building code council—Duties—Public meetings—Timing of code changes.
19.27.076 - State building code council—Open public access information technologies.
19.27.077 - State building code council—Mobile on-demand gasoline operations—Adoption of rules—Fees.
19.27.080 - Chapters of RCW not affected.
19.27.085 - Building code council account—Building permit fee.
19.27.087 - Building permit and plan review fees—Agricultural structures.
19.27.090 - Local jurisdictions reserved.
19.27.095 - Building permit application—Consideration—Requirements.
19.27.100 - Cities, towns, counties may impose fees different from state building code.
19.27.111 - RCW 19.27.080 not affected.
19.27.113 - Automatic fire-extinguishing systems for certain school buildings.
19.27.140 - Copy of permit to county assessor.
19.27.150 - Report to department of enterprise services.
19.27.175 - Recycled materials—Study code and adopt changes.
19.27.190 - Indoor air quality—Interim and final requirements for maintenance.
19.27.195 - Renewable energy systems—Study code and adopt changes.
19.27.490 - Fish habitat enhancement project.
19.27.500 - Nightclubs—Automatic sprinkler system—Building code council shall adopt rules.
19.27.510 - "Nightclub" defined.
19.27.520 - Building constructed, used, or converted to nightclub—In accordance with chapter.
19.27.530 - Carbon monoxide alarms—Requirements—Exemptions—Adoption of rules.
19.27.540 - Electric vehicle infrastructure requirements—Rules.
19.27.550 - Accessible parking space access aisles.
19.27.560 - International Wildland Urban Interface Code.
19.27.570 - Mass timber products—Building construction.
19.27.580 - Use of substitutes—Adoption of rules.
19.27.720 - Inspections and tests—Qualifications—Report—Penalty.