Sec. 13.
The fill pipe for such tank or tanks shall be galvanized iron or steel not less than 1 1/2 inches in diameter, extending to the outside of any building, and shall be properly capped at all times. All storage tanks for fuel oil shall be provided with a vent pipe not less than 3/4 inch in diameter with a return bend on the open or exposed end, and the outside opening of such vent pipe, or manhole in outside tanks, shall be covered by a non-corrodible wire screen of 30 by 30 mesh: Provided, however, That vent pipe of such storage tank inside of any building shall terminate on the outside of the building, not less than 10 feet above the source of supply, and that vent pipes from underground storage tanks outside of any building shall not be less than 1 1/4 inches inside diameter and shall terminate not less than 2 feet above grade line. The vent pipe from 2 or more tanks may be connected to 1 upright provided they be connected at a point at least 12 inches above the source of supply.
History: 1929, Act 319, Imd. Eff. May 28, 1929 ;-- CL 1929, 2620 ;-- CL 1948, 125.563
Structure Michigan Compiled Laws
Chapter 125 - Planning, Housing, and Zoning
Act 319 of 1929 - Fuel Oil (125.551 - 125.575)
Section 125.551 - Fuel Oil; Adoption of Act; Scope of Act Restricted.
Section 125.552 - Fuel Oil; Definitions.
Section 125.553 - Installation Permit; Temporary Tag; Inspection; Existing Plants; Fees.
Section 125.554 - Prohibited Furnishing of Fuel Oil.
Section 125.555 - Flash Point; Tester; Mixing or Blending; Waste Oil.
Section 125.556 - Scope of Tests.
Section 125.557 - Oil Burners; Equipment.
Section 125.558 - Oil Burners; Automatic Ignition.
Section 125.559 - Pipes; Joints; Valves; Packing Gland.
Section 125.560 - Electrical Installations.
Section 125.561 - Dampers; Ventilation; Instructions, Posting; Extinguisher.
Section 125.562 - Oil Storage Tanks; Construction, User; Storage Limit.
Section 125.563 - Oil Storage Tanks; Fill Pipe; Vent Pipe.
Section 125.564 - Oil Storage; Limitations.
Section 125.565 - Tanks Located Underground.
Section 125.566 - Installation of Inside Tanks.
Section 125.567 - Underground Tanks Incased.
Section 125.568 - Measuring Devices.
Section 125.569 - Metal Gauge.
Section 125.570 - Tanks; Construction, Testing; Underwriter's Label.
Section 125.571 - Required Equipment; Gravity, Water Pressure or Suction Burners.
Section 125.572 - Required Equipment; Burners Connected With Heating System.
Section 125.573 - Gases Prohibited in Gas Pilot.