(225 ILCS 705/Art. 18 heading)
(225 ILCS 705/18.01) (from Ch. 96 1/2, par. 1801)
Sec. 18.01.
After the effective date of this Act, overhead power lines on
the surface, carrying greater than 600 volts potential, shall be installed
on insulators and shall be supported and guarded against contact with other
circuits.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.02) (from Ch. 96 1/2, par. 1802)
Sec. 18.02.
Power circuits on the surface shall be protected against
lightning.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.03) (from Ch. 96 1/2, par. 1803)
Sec. 18.03.
Electric wiring shall be installed so as to present minimum fire
and contact hazards in buildings on the surface.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.04) (from Ch. 96 1/2, par. 1804)
Sec. 18.04.
Permanent surface transformers shall be elevated eight feet or
more above the ground, or be enclosed in a transformer house, or be
surrounded by a fence at least 6 feet high.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.05) (from Ch. 96 1/2, par. 1805)
Sec. 18.05.
Transformers containing flammable oil and installed on the
surface, if the transformers are located within 10 feet of mine openings,
shall be provided with a drain, or catch basin, to confine the oil.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.06) (from Ch. 96 1/2, par. 1806)
Sec. 18.06.
The operator of every mine where motor generator sets or
transformers are installed underground shall designate or cause to be
designated on the map provided for in this Act, the location of transformer
stations and motor generator stations and said stations shall be of
fireproof construction. A sufficient amount of sand or rockdust shall be
kept in a suitable place convenient to motor generator stations and
transformer stations for the purpose of extinguishing any fire starting
from short circuiting or otherwise. In addition thereto two suitable
chemical fire extinguishers shall be kept in a convenient place.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.07) (from Ch. 96 1/2, par. 1807)
Sec. 18.07.
"DANGER-HIGH VOLTAGE" signs shall be posted conspicuously on
all transformer stations, high-voltage switchboards and other
installations.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.08) (from Ch. 96 1/2, par. 1808)
Sec. 18.08.
Pull switches, circuit breakers, and other power controls shall
be mounted on slate or other insulating material of equal or superior
insulating qualities.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.09) (from Ch. 96 1/2, par. 1809)
Sec. 18.09.
All wires carrying electric current passing through curtains or
flammable material, shall be properly protected so as not to ignite said
curtains or flammable material.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.10) (from Ch. 96 1/2, par. 1810)
Sec. 18.10.
When the main line track is used as a return conductor, both
rails shall be well-bonded at every joint, and one rail on secondary
haulage roads, when used as a return conductor, shall be bonded, unless
other equally efficient methods are used.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.11) (from Ch. 96 1/2, par. 1811)
Sec. 18.11.
All trolley and positive feed wires crossing places where
persons or animals are required to travel, shall be safely guarded or
protected from such persons or animals coming in contact therewith.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.12) (from Ch. 96 1/2, par. 1812)
Sec. 18.12.
Casings of transformers shall be grounded effectively.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.13) (from Ch. 96 1/2, par. 1813)
Sec. 18.13.
All main power circuits entering the mine from the outside shall
have disconnecting switches above and below ground.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.14) (from Ch. 96 1/2, par. 1814)
Sec. 18.14.
Electric light wires shall be supported by suitable insulators.
Electric lights shall be installed so that they cannot come in contact with
combustible materials.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.15) (from Ch. 96 1/2, par. 1815)
Sec. 18.15.
Dry wooden platforms, rubber mats, or other electrically
non-conductive material shall be kept in place at each switchboard and
power-control switch; and at stationary machinery where shock hazards
exist.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.16) (from Ch. 96 1/2, par. 1816)
Sec. 18.16.
Trolley wires or other exposed electrical wires shall not carry
more than 275 volts. Terminal ends of all positive wires shall be guarded
against persons coming in contact therewith.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.17) (from Ch. 96 1/2, par. 1817)
Sec. 18.17.
In a gassy mine, permissible junction or distribution boxes
shall be used for making multiple-power connections in working places or
other places where dangerous quantities of methane may be present or may
enter the air current, except that where nonpermissible junction or
distribution boxes are in use, or on order, on the effective date of this
section or the date such mine became a gassy mine, whichever is later,
their use may be continued until such time as replacements are made.
(Source: Laws 1953, p. 701.)
(225 ILCS 705/18.18) (from Ch. 96 1/2, par. 1818)
Sec. 18.18.
In all mines, trolley and feeder wires shall not extend beyond
the last open crosscut and shall be kept at least 150 feet from pillar
workings.
(Source: Laws 1957, p. 2413.)
Structure Illinois Compiled Statutes
Chapter 225 - PROFESSIONS, OCCUPATIONS, AND BUSINESS OPERATIONS
225 ILCS 705/ - Coal Mining Act.
Article 1 - Short Title - Definition of Terms
Article 2 - Administration Of Act: Mining Board Organization And Duties
Article 3 - New Mines--Certificates Of Competency--Credentials And Examinations
Article 4 - State Mine Inspectors and Mine Inspection
Article 5 - Mine Manager--Requirements And Duties
Article 6 - Mine Examiners--Requirements And Duties
Article 7 - Hoisting Engineer And Hoisting
Article 8 - Miners' Examinations
Article 9 - Employment Of Boys And Women
Article 10 - Accidents And Injuries
Article 12 - Analytical Laboratory
Article 13 - Miscellaneous Regulations
Article 14 - Buildings On Surface
Article 17 - Crosscuts And Stoppings
Article 18 - Electricity Regulations
Article 20 - Permissible Explosives And Regulations For Breaking Down Coal
Article 21 - Fire Prevention And Fire Control
Article 22 - Haulage And Transportation Underground
Article 23 - Refuge Underground
Article 24 - Rock Dust And Coal Dust
Article 25 - Safety Lamps And Barometers
Article 27 - Drillers And Shooters Or Shot Firers
Article 29 - Telephone and Wireless Communication Systems
Article 31 - Ventilation, Mine Gases And Gassy Mine Classification
Article 32 - Weighman And Scales